1. Baseline and operating conditions |
Influence quantity Base condition Operating conditions |
Ambient temperature |
23ºC±1ºC-10ºC ~ 40ºC |
Environmental wet crossing |
40% ~ 60% < 80% |
Instrument operating voltage |
9V±0.1V9V±1.5V |
Auxiliary grounding resistance |
< 100Ω < 30kΩrC, rP |
Interference voltage |
< 20V |
Interference current |
< 2A |
Electrode spacing during R measurement |
a > 5da > 5d |
Electrode spacing when measuring ρ |
a > 20ha > 20h |
2. General specification |
Power |
two, three, four wire measurement ground resistance, soil resistivity; Grounding voltage and AC voltage measurement |
Power source |
DC 9V (alkaline dry battery LR14 1.5V 6, continuous standby 300 hours) |
Measuring range |
Ground resistance: 0.00Ω ~ 30.00kΩ; Soil resistivity: 0.00Ωm ~ 9000kΩm; Grounding voltage: 0V to 600V |
Measurement method |
precision 4-wire, 3-wire method measurement, simple 2-wire grounding resistance measurement |
Measuring method |
Ground resistance: rated current pole-changing method, measuring current 20mA Max |
Soil resistivity |
Quadrupole method (Wenner method) |
Voltage to ground |
average rectification (P(S)-ES interface) |
Test frequency |
128Hz/111Hz/105Hz/94Hz(AFC) |
Short-circuit test current |
AC 20mA max |
Open circuit test voltage |
AC 40V max |
Test voltage waveform |
sine wave |
Electrode spacing range |
1m ~ 100m can be set |
Shift |
Ground resistance: 0.00Ω ~ 30.00kΩ automatic shift; Soil resistivity: 0.00Ωm ~ 9000kΩm automatic shift |
Backlight |
controllable white screen backlight, suitable for use in dim places |
Display mode |
4-bit large LCD display with white backlight |
Measurement indication |
LED flashing during measurement, LCD backward counting, progress bar chart indication |
LCD size |
128mm x 75mm |
LCD display area |
124mm x 67mm |
Instrument size |
Height width: 215mm×190mm×95mm |
There are four standard test lines |
red 20m, black 20m, yellow 10m, and green 10m each |
2 simple test lines |
red 1.6m, black 1.6m each |
Four auxiliary ground rods |
φ10mm x 150mm |
Measuring time |
Voltage to ground: about 3 times/second; Ground resistance, soil resistivity: about 5 seconds/time |
Measurement times |
more than 5000 times (short circuit test, test once, stop for 30 seconds and test again) |
Line voltage |
Measured below AC 600V |
RS232 interface |
With RS232 interface, software monitoring, stored data can be uploaded to the computer, save and print |
Communication line |
1 RS232 communication line, 1.5m long |
Data storage |
300 groups, "MEM" storage indication, display "FULL" symbol indicates that the storage is full |
Data HOLD |
The "hold" symbol indicates when data is held |
Data access |
The "READ" symbol indicates when data is accessed |
Overflow display |
The "OL" symbol indicates when overrange overflow |
Interference test |
automatic identification of interference signals, interference voltage is higher than 5V "NOISE" symbol indication |
Auxiliary grounding test |
with auxiliary grounding resistance test function, 0.00KΩ ~ 30kΩ(100R+rC< 50kΩ, 100R+rP< 50 k Ω) |
Alarm function |
When the measured value exceeds the alarm setting value, "dud-dud-dud-dud-" alarm prompt |
Battery voltage |
When the battery voltage drops to about 7.5V, the battery low voltage symbol "is displayed to remind you to replace the battery |
Power consumption |
Standby: about 20mA(backlight off); Turn on the backlight: about 45mA(backlight off 25mA); Measurement: Approx. 100mA(backlight off) |
Quality |
Total weight: 4.5kg(including packaging); Instrument: 1443g(including battery); Test line: 1560g; Auxiliary ground rod: 935g(4) |
Working temperature and humidity |
-10ºC ~ 40ºC; Less than 80%rh |
Storage temperature and humidity |
-20ºC ~ 60ºC; Below 70%rh |
Overload protection |
Measuring ground resistance: C(H)-E, P(S)-ES AC 280V/3 seconds between ports |
Insulation resistance |
more than 20MΩ (500V between circuit and housing) |
Voltage resistance |
AC 3700V/rms(between circuit and housing) |
Electromagnetic characteristics |
IEC61326(EMC) |
Suitable for safety |
IEC61010-1(CAT 300V, CAT IV 150V, pollution level 2); IEC61010-031; IEC61557-1(ground resistance); IEC61557-5(Soil resistivity); JJG 366-2004. |