high voltage generator
Technical features:
High frequency voltage doubling circuit, PWM pulse width modulation technology and high power IGBT devices.
Large voltage feedback, high output voltage stability, ripple coefficient ≤1%.
Range smooth voltage regulation, voltage regulation fineness good adjustment accuracy ≤0.5%, stability ≤1%, voltage and current error 1% (reading ±0.2KV), current error ±1 word.
Zero voltage boost potentiometer.
75%UDC1mA function button, convenient zinc oxide arrester test, accuracy 1% reading ±1%.
Overvoltage protection using code setting, clear at a glance, error ±1%.
Pressure doubling using new materials, light and strong. Appearance coated with special insulation material, good electrical performance, strong moisture resistance.
Folding support foot, large diameter area, good stability.
Integrated design, high voltage mop cable leading, convenient field test.
The products meet the technical requirements of DL/T848.1-2004, and have passed the type test of the electrical equipment quality testing center of the Ministry of Power, and strictly implement the enterprise standard factory.
high voltage generator
all-in-one
specification
Technical parameter
|
40/3 |
60/2 |
60/3 |
60/5 |
80/2 |
100/2 |
120/2 |
120/5 |
Rated voltage (kV) |
40 |
60 |
60 |
60 |
80 |
100 |
120 |
120 |
Rated current (mA) |
3 |
2 |
3 |
5 |
2 |
2 |
2 |
5 |
Rated power (W) |
120 |
120 |
180 |
300 |
160 |
200 |
240 |
600 |
Chassis weight (kg) |
7 |
10.5 |
10.5 |
10.5 |
11 |
11.2 |
11.2 |
11.2 |
Pressure doubling weight (kg) |
One2.5 |
2.7 |
2.7 |
2.7 |
3.0 |
3.3 |
3.3 |
3.3 |
Pressure doubling height (mm) |
One400 |
400 |
400 |
400 |
400 |
500 |
500 |
500 |
Voltage measurement accuracy |
Digital display meter ± (1.0% reading ±2 words) |
Current measurement accuracy |
Digital display meter ± (1.0% reading ±2 words) |
Ripple coefficient |
≤1% |
Voltage stability |
Random fluctuation, power supply voltage change ±10% ≤1% |
Overload capacity |
The no-load voltage can exceed the rated voltage by 10% for ten minutes
The maximum charging current is 1.5 times the rated current |
Power source |
Single-phase AC 50Hz 220V±10% |
Working mode |
Intermittent use |
The maximum continuous duration is 30 minutes |
Working environment |
Temperature: -10 ~ 40ºC |
Relative humidity: not more than 85% at room temperature of 25ºC (no condensation) |
Altitude: Below 1500 meters |
With capacitive load capacity |
There is no limit to the electrical capacity of the subject |
It can be charged at 1.5 times the rated current |
Structural characteristics |
Epoxy glass fiber reinforced plastic electrically insulated pressure doubling cylinder
|
Air insulation, no leakage |
Operating box characteristics |
High-precision 0.75UDC1mA single-touch button (accuracy ≤1.0%) suitable for zinc oxide arrester test |
Overvoltage protection is set at a glance |
Split machine
specification
Technical parameter |
400/10 |
400/20 |
450/20 |
500/10 |
500/20 |
500/40 |
Rated output
Voltage (kV) |
400 |
400 |
450 |
500 |
500 |
500 |
Rated output
Current (mA) |
10 |
20 |
20 |
10 |
20 |
40 |
Rated output
Power (W) |
4000 |
8000 |
9000 |
5000 |
10000 |
20000 |
Maximum charge
Current (mA) |
15 |
30 |
40 |
15 |
30 |
60 |
Voltage measurement error |
±1%(full degree)±2 words |
Current measurement error |
±1%(full degree)±2 words |
Overvoltage setting error |
≤1% |
0.75 Switching error |
≤1% |
Ripple coefficient |
≤0.5% |
Voltage stability |
Random fluctuation, power supply voltage change ±10%, ≤1.0% |
Working mode |
Intermittent use: rated load 30 minutes
1.1 times rated voltage use: 10 minutes |
Ambient humidity |
-10ºC~40ºC |
Relative humidit |
not more than 85% when the temperature is 25ºC (no condensation) |
altitude |
Below 1500 meters |
high voltage generator