Customization: | Available |
---|---|
After-sales Service: | Online |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 3000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
Product Introduction
KGJF-OL type office on-line monitoring device is a real-time online monitoring device for substation GIS office, which is mainly suitable for office on-line monitoring, analysis and remote alarm of digital substations with voltage levels of 110kV and above, so as to realize the digitalization of substation maintenance.
KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
Product Characteristics
1, high sensitivity. The detection sensitivity of metal particles and floating potential body discharge can reach 5PC, and the partial discharge emitted by corona and creepage can be accurately detected.
2, good stability. The selection of high-quality sensors, external noise sensors and special filters, the use of advanced detection technology, with software processing technology, so that the anti-interference is strong, effectively improve the stability of the instrument.
3, accurate judgment. The device continuously samples in real time, and only when the detected partial discharge signal meets the set "threshold", "density" and "credibility" at the same time, it is judged as abnormal, and the judgment accuracy is improved.
4, perfect data analysis function. The device has a perfect record to analyze the phenomenon of office release during GIS operation, determine the occurrence and development law of office release, and provide a basis for maintenance.
5, local and remote alarm. The device is equipped with local sound and light alarm function and remote software interface alarm function.
6, the device adopts RS485 communication, communication distance is long and reliable.
KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
Products Certificate
ISO9001
a)Mechanical and environmental parameters
Table 2-1 Mechanical and environmental parameters of the device
Chassis structure size: |
482.6mm×88.0mm×300.0mm(Width x height x depth) |
normal working temperature |
-10ºC~50ºC |
working temperature limit |
-20ºC~60ºC |
Storage and transportation: |
-25ºC~70ºC |
relative humidity |
5%~95% |
barometric pressure |
86~106KPa |
b) Rated electrical parameter
Table 2-2 Rated electrical parameters of the device
frequency |
50Hz/60Hz |
Ac power supply: |
AC220V,50Hz/60Hz allowable deviation:-20%~+15% |
power dissipation |
0.5VA |
After the device is subjected to the above overload voltage/current, the insulation performance does not decrease. |
working power supply |
AC220V,50Hz/60Hz allowable deviation:-20%~+15% |
working current |
0.5A |
Host monitoring frequency band: |
300MHz-2000MHz(high frequency) ,300MHz-3000MHz(noise |
sensitivity |
5PC |
transmission gain |
85dB |
standing-wave ratio (SWR) |
1.5 |
Number of detection channels: |
4 High frequency, 4 noise |
impedance |
50 Ohm |
impedance |
N-type |
communication interface |
RS485 |
synchronous processing |
Software synchronization and AC power synchronization |
acquisition accuracy |
12Bit |