• Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
  • Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
  • Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
  • Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
  • Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
  • Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001

Kgjl-Ol Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001

After-sales Service: Online
Warranty: 1 Year
Type: Discharge Online Monitoring Device
Maxcapacity: <1000KN
Accuracy Grade: 1
Load Way: Electronic Load
Samples:
US$ 3000/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2023

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
KGJL-OL
Display
Digital
Control
Computer Control
Weight
200kg
Power Source
AC220V
Transport Package
Plywood Cases
Specification
60*50*80cm
Trademark
LONROY
Origin
Guangdong
HS Code
9024800000
Production Capacity
200

Product Description

KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001

Product Introduction
KGJF-OL type office on-line monitoring device is a real-time online monitoring device for substation GIS office, which is mainly suitable for office on-line monitoring, analysis and remote alarm of digital substations with voltage levels of 110kV and above, so as to realize the digitalization of substation maintenance.

 

KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001

Product Characteristics
1, high sensitivity. The detection sensitivity of metal particles and floating potential body discharge can reach 5PC, and the partial discharge emitted by corona and creepage can be accurately detected.
2, good stability. The selection of high-quality sensors, external noise sensors and special filters, the use of advanced detection technology, with software processing technology, so that the anti-interference is strong, effectively improve the stability of the instrument.
3, accurate judgment. The device continuously samples in real time, and only when the detected partial discharge signal meets the set "threshold", "density" and "credibility" at the same time, it is judged as abnormal, and the judgment accuracy is improved.
4, perfect data analysis function. The device has a perfect record to analyze the phenomenon of office release during GIS operation, determine the occurrence and development law of office release, and provide a basis for maintenance.
5, local and remote alarm. The device is equipped with local sound and light alarm function and remote software interface alarm function.
6, the device adopts RS485 communication, communication distance is long and reliable.

 

KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001

Products Certificate

ISO9001

 
KGJL-OL Partial Discharge Online Monitoring Device Power Electric Energy Measurement ISO9001
Product Parameters

a)Mechanical and environmental parameters
Table 2-1 Mechanical and environmental parameters of the device

Chassis structure size:

482.6mm×88.0mm×300.0mm(Width x height x depth)                   

normal working temperature

-10ºC~50ºC

working temperature limit

-20ºC~60ºC

Storage and transportation:

-25ºC~70ºC

relative humidity

5%~95%

barometric pressure

86~106KPa

 

b) Rated electrical parameter
Table 2-2 Rated electrical parameters of the device

frequency         

50Hz/60Hz

Ac power supply:    

AC220V,50Hz/60Hz

allowable deviation:-20%~+15%            

power dissipation

0.5VA

After the device is subjected to the above overload voltage/current, the insulation performance does not decrease.


c) Main technical index
i. Device technical parameters

working power supply

AC220V,50Hz/60Hz   

allowable deviation:-20%~+15%

working current

0.5A

Host monitoring frequency band:

300MHz-2000MHz(high frequency) ,300MHz-3000MHz(noise
)

sensitivity

5PC

transmission gain

85dB

standing-wave ratio (SWR)

1.5

Number of detection channels:

4 High frequency, 4 noise

impedance

50 Ohm

impedance

N-type

communication interface

RS485

synchronous processing

Software synchronization and AC power synchronization

acquisition accuracy

12Bit