Customization: | Available |
---|---|
After-sales Service: | Online |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 3000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KGXZ Frequency Conversion Resonance Machine AC Resonant Test System for Generators ISO9001
Product Introduction
KGXZ transformer substation frequency conversion series resonance test device is mainly designed and manufactured for the AC voltage withstand test of primary electrical equipment in substations of 220kV and below. It can meet the AC voltage withstand test of transformer, GIS system, SF6 switch, cable, sleeve and other capacitive equipment according to the specification requirements. Transformer substation frequency conversion series resonance test device can not only meet the requirements of high voltage, low current equipment test conditions, but also meet the requirements of low voltage, high current equipment test conditions, with a wide range of application, is the local, city, county high voltage test departments and power installation, repair and test engineering units ideal voltage equipment.
The frequency conversion series resonance test device of KGXZ substation is mainly composed of frequency conversion control power supply, excitation transformer, reactor and capacitance divider. The frequency conversion control power supply adopts the imported special SPWM digital waveform generator chip, the frequency resolution is 16 bits, and the frequency fineness can reach 0.1Hz when it is 20 ~ 300Hz. At the same time, the orthogonal non-synchronous fixed carrier modulation is adopted to ensure the output waveform is good in the whole frequency range. The power part adopts the advanced IPM module to ensure the stability and safety of the instrument.
KGXZ Frequency Conversion Resonance Machine AC Resonant Test System for Generators ISO9001
Product Characteristics
1, the reactor with the same voltage level and the same capacity is smaller in size and lighter in weight; Low temperature rise at rated load; Using dry epoxy casting, high mechanical strength, good electrical insulation performance, beautiful and reliable.
2, variable frequency power control box capacity margin; Strong protection function; Good output waveform; Good stability; With a variety of working modes, easy to operate; Single-phase 220V or three-phase 380V input power supply is universal, convenient on-site power supply.
3, flexible configuration. Different types of reactors can be selected to meet the requirements of different samples, to achieve multi-purpose, cost-effective.
Quota output voltage |
0~1000kV And below |
output frequency | 30~300Hz |
Resonant voltage waveform | Pure sine wave, waveform distortion ≤1.0% |
working system | Continuous working time at full power 60min |
quality factor | 30~90 |
Frequency regulation sensitivity | 0.1Hz |
degree of instability | <0.05% |
working power supply | Single 220V or three-phase 380V±10% |
Power frequency 50Hz±5% |
KGXZ Frequency Conversion Resonance Machine AC Resonant Test System for Generators ISO9001
Trial scope
Product model name | Application range (10kV ~ 500kV voltage level substation electrical equipment AC voltage withstand equipment, frequency 30 ~ 300Hz) | ||||
Variable frequency source | Resonant reactor | exciting transformer |
voltage divider |
range of application | |
KGXZ-B-50/50/25 | 3kW |
25kV/1A two sets |
3kVA (dry) | 50kV | nbsp; 1000kVA and below 10kV power conversion 10kV switch, bus bar, PT, CT, etc 10kV(300mm2) cable ≤1.0km |
KGXZ -B-108/108/27 | 5kW | 27kV/1A Four Sets (dry) |
5kVA (dry) | 110kV | 31500kVA and below 35kV power conversion 35kV switch, bus bar, PT, CT, etc 10kV(300mm2) cable 2km 35kV (300mm2) cable 0.5km |
KGXZ -B-200/200/50 | 10kW | 50kV/1A Four Sets (dry) |
10kVA (dry) | 200kV | 5000KVA and below 110kV power conversion 110kVGIS, PT, CT, etc. (Preventive test) 35kV(300mm2) cable ≤1.0km 10kV (300mm2) cable ≤2.0km |