Product Introduction
TAG-8600 wireless high voltage nuclear phase meter is used for phase verification and phase sequence verification of high voltage power lines and substations. It adopts the latest power electronic testing technology and wireless transmission technology, safe and reliable operation, easy to use, overcome many shortcomings of wired nuclear phase device, in line with the national power safety equipment quality supervision and inspection.
IEC61481-A2 Wireless High Voltage Nuclear Phase Meter Nuclear Electric Power Circuit Phase Detector
Product Characteristics
1, can measure high and low voltage wireless speech nuclear phase, frequency, phase, phase sequence, electrical testing.
2, display mode: 3.5 inch true color LCD display
IEC61481-A2 Wireless High Voltage Nuclear Phase Meter Nuclear Electric Power Circuit Phase Detector
Product Parameters
Work and energy |
High and low voltage wireless speech nuclear phase, frequency, phase, phase sequence, electrical testing |
Electric source | DC 3.7V rechargeable lithium battery, USB charging interface, continuous working for about 10 hours |
transmission mode | 315MHz,433MHz wireless transmission |
Nuclear phase distance | About 160m Max |
display mode | 3.5 "true color LCD display |
Range | Nuclear phase voltage level: AC 10V ~ 550kV |
phase position:0.0°~360.0° | |
frequency:45Hz~75Hz | |
resolution | 0.1°;0.1Hz |
Precision (23ºC±5ºC, below 80%RH) | phase position:≤±10° |
phase position:≤±2Hz | |
Phase differentiation | In-phase :-30° ~ 30°; Out of phase: 90° ~ 150° and 210° ~ 270° |
phonetic function | In-phase, out-of-phase, X signal normal, Y signal normal and other voice functions |
Insulation rod size | After stretching, the length is about 3.2m. Approx. 0.6m after shrinkage (optional 5 m rod) |
data storage | 9999 group |
Nuclear phase mode | Contact nuclear phase: the bare wire below 35kV, or the wire with safety insulation skin below 110kV directly contact the nuclear phase. (with insulated rod operation) |
Non-contact nuclear phase: bare wires above 35kV, or lines above 110kV using non-contact nuclear phase, gradually close to the wire. (with insulated rod operation) | |
Charge indicator | The detector beeps "du-du-du-duk" |
shift | automatic gear change |
sample rate | 2 times per second |
meter size | Detector: Length, width and thickness 145mm×60mm×48mm |
Receiver: Length, width and thickness 250mm×100mm×40mm | |
Backlight control | Press the up and down arrow keys to adjust the backlight brightness |
Induction intensity control |
According to the induced electric field strength, the detector can automatically control the magnification, which is convenient for the nuclear phase where the line is dense |
data-hold |
In test mode, press the HOLD key to HOLD data, and then press the Hold key to cancel the hold |
Exit Function |
Press ESC to exit the current function screen and return to the upper-level directory |
World Data Referral Centre | Press ENTER to enter the data view mode, press the arrow key to browse the saved data |
No-signal indication | The "----" symbol is displayed dynamically when the receiver does not receive the transmission signal |
automatic shut |
After about 15 minutes of power on, the meter automatically shuts down to reduce battery consumption |
automatic shut | When the battery voltage is below 3.2V: Detector: The power indicator blinks slowly, reminding to charge; Receiving end: The battery low voltage symbol is displayed, reminding to charge |
rated current | Detector: 35mA max; Receiver: 300mA max |
Instrument quality | Detector: 205g(including battery) |
Receiver: 395g(battery included) | |
Insulation rod: 1.2kg (3m rod), 1.45kg(5m rod) | |
Total mass: 7kg(including instrument box, equipped with 5 meter rod and box about 9.8kg) | |
Operating temperature and humidity | Operating temperature and humidity |
Storage temperature and humidity | -10ºC ~ 60ºC; Below 70%Rh |
Dry disturbance | No extra-strong electromagnetic field; No 433MHz, 315MHz same frequency interference |
dielectric strength |
Insulation rod: AC 110kV/rms(after the insulation rod is fully stretched, between the two ends) |
Detector: 2000V/rms(between the two ends of the housing) |
|
Receiver: 2000V/rms(between the two ends of the housing) |
|
structure |
Drip proof Type II, IP63 |
Fit for safety
|
GB13398-92,GB311.1-311.6-8,3DL408-91
Standard and the new national power industry standard "1kV ~ 35kV portable nuclear phase device general technical conditions DL/T971-2005" requirements |
Comply with IEC61481-A2:2004; IEC 61243-1 ed.2:2003 standard |