• Transformer Tap-Changer on-Load-Transition Resistance Tester
  • Transformer Tap-Changer on-Load-Transition Resistance Tester
  • Transformer Tap-Changer on-Load-Transition Resistance Tester
  • Transformer Tap-Changer on-Load-Transition Resistance Tester
  • Transformer Tap-Changer on-Load-Transition Resistance Tester
  • Transformer Tap-Changer on-Load-Transition Resistance Tester

Transformer Tap-Changer on-Load-Transition Resistance Tester

After-sales Service: Online
Warranty: 1 Year
Type: Transformer Tap-Changer Resistance Tester
Control: Computer Control
Weight: 0-100Kg
Power Source: AC220V
Customization:
Diamond Member Since 2023

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
KDKC-2010
Transport Package
Plywood Case
Trademark
LONROY
Origin
China
HS Code
9024800000
Production Capacity
200pieces/Month

Product Description

Transformer tap-changer on-load-transition resistance tester

Product characteristics
1, test Y0, Y, △ type transformer, resistance value without conversion directly display.
2. Humanized data analysis can automatically find out the fault in the middle of the waveform and make a mark.
3, waveform display is based on the sampled data automatically adjust the resistance value and time amplitude.
4, can be tested with winding or without winding.
5, four-terminal wiring, providing high-precision resistance measurement, and no wire compensation.
6, in the middle of the test can be continuous test, saving the transformer power failure time.
7, the transformer on-load switch tester can generate word report, convenient data management and query.
8, the instrument is controlled by a small computer, equipped with 800×480 color LCD touch screen.
9, high-speed printer, support external mouse, easy to operate.
10, the instrument can automatically save 1000 sets of data inside, and can also be stored with external U disk.

Transformer tap-changer on-load-transition resistance tester

Three independent test power supply, 3A/1A 0.6A/0.2A file
port maximum voltage 24V
 the instrument set sampling rate 10 ~ 30KHz;
 resistance measurement range 0.3 ~ 40Ω
voltage mode 1A: 0.4Ω ~ 20Ω 0.2A: 10Ω ~ 100Ω
 transition resistance range 100Ω
resistance resolution 0.05Ω
accuracy transition resistance: ±5% reading ±0.1Ω
time measurement range 1ms ~ 300ms
time resolution 0.1ms
time measurement accuracy 1ms ~ 100ms±0.1ms; 100ms ~ 300ms±1%
accuracy  transition time: ±0.5% reading ±0.2mS
three-phase synchronization  0.1ms; Sampling frequency: 10~20KHz
 processing part high-speed 32-bit microprocessor, storage waveform up to 1000 groups
high-speed A/D converter, the highest sampling rate up to 400KHZ;
power supply AC220V10%; Power 180W.
 size 420mm*350mm*220mm.
 Weight 12kg