Ultrasonic flaw detector/Switchgear partial discharge detector tester
This product can be applied to the local discharge detection of power system, including high-voltage switch cabinet, ring network cabinet, voltage/current transformer, transformer (including dry transformer), GIS, overhead lines, cables and other equipment insulation state detection, through the following indicators to measure the discharge degree of electrical equipment:
Partial discharge intensity detection: By measuring the discharge signal in one power frequency cycle, the intensity of partial discharge is characterized according to the maximum value (dB) in the discharge pulse sequence.
Partial discharge frequency detection: By measuring the discharge signal in one power frequency cycle, the discharge pulse is extracted and the frequency of partial discharge is characterized according to the number of discharge pulses.
Ultrasonic flaw detector/Switchgear partial discharge detector tester
Product Features
Different sensors were configured to realize partial discharge detection of electrical equipment.
Humanized man-machine interface to facilitate the data management of different equipment;
Built-in ultrasonic sensor and transient ground voltage (TEV) sensor, external transformer, GIS, overhead line, cable and other special sensors;
Non-intrusive detection method, no power outage during the test process, no additional configuration of high voltage source, more convenient than the traditional pulse partial discharge detector;
The test bandwidth ranges from 30kHz to 2.0GHz, which is suitable for various frequency bands.
Product application field
Power supply and distribution enterprises;
Railway system;
Petrochemical power supply system;
Aerospace testing field;
Automatic detection field;
Ultrasonic flaw detector/Switchgear partial discharge detector tester
TEV measurement |
UHF measurement |
Range of measurement |
0-60 dBmV |
Detection frequency band |
300-2000MHz |
resolution |
1dB |
Range of measurement |
0-60 dBmV |
accuracy |
±1dB |
accuracy |
<1dBmV |
Maximum pulse per cycle |
1400 |
Sensor frequency band |
300-2000MHz |
Measuring frequency band |
3~100MHz
|
AA measurement |
AE measurement |
Range of measurement |
-6dBμV~68dBμV |
Range of measurement |
-6dBμV to 68dBμV |
resolution |
1dB |
resolution |
1dB |
accuracy |
±1dB |
accuracy |
±1dB |
Sensor center frequency |
40 kHz |
Range of frequency |
20~200 kHz |
HFCT measurement |
Sensor transmission impedance |
5mV/mA |
Frequency of detection |
1~30MHz |
sensitivity |
≤50pC |
hardware |
shell |
ABS |
display |
4.0 inch RGB LCD display resolution: 800*480 |
connector |
USB port (also charger input)
3.5mm stereo headphone jack
External sensor input interface
|
Headphones |
Minimum 8 ohms |
SD card |
Standard 16G ~ 64G |
Built-in battery |
3.7V/5000mAh lithium battery
|
Working hours |
About 6 hours |
charger
|
AC 90-264V or DC 5V |
Temperature of service |
-20 ~ 50ºC |
humidity |
20-85% relative humidity |
Volume and weight |
210*100*35(mm) 0.4KG(host) |