Customization: | Available |
---|---|
After-sales Service: | Online |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 3000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KGHG-B3 Transformer Characteristics Comprehensive Instrument CT PT Current Analyzer ISO9001
Product Introduction
KGHG-B3 transformer characteristic tester is used for automatic testing of protective, metering or TPY transformers, suitable for laboratory or field testing. Supports the detection of CT and PT (protection class, measurement class, TP class) steady and instantaneous parameters. The test is simple and convenient, one key to complete the CT direct resistance, excitation, ratio and polarity test, and in addition to the load test, the other tests of CT are the same wiring mode.
KGHG-B3 Transformer Characteristics Comprehensive Instrument CT PT Current Analyzer ISO9001
Product Characteristics
1, support the detection of CT and PT (protection, measurement, TP) steady and instantaneous parameters.
2, meet GB1207, GB1208, GB16847 (IEC60044-1, IEC60044-6) and other regulations requirements.
3, the use of advanced power technology, excitation voltage up to 30KV.
4, no need to connect other auxiliary equipment, single machine can complete all the test items.
5, the test is simple and convenient, one key to complete the CT direct resistance, excitation, ratio and polarity test, and in addition to the load test, the other tests of CT are the same wiring method.
6, with micro fast printer, can directly print test results on site.
7, intelligent controller, simple operation.
8, large screen LCD, graphical display interface.
9, automatically give the CT/PT (excitation) inflection point value according to the procedure.
10, automatically give 5% and 10% error curves.
11, can save 3000 sets of test data, not lost after power failure.
12, support U disk transfer data, can be read through a standard PC, and generate WORD reports.
13, small and light < 10Kg, very conducive to field testing.
KGHG-B3 Transformer Characteristics Comprehensive Instrument CT PT Current Analyzer ISO9001
Item |
Parameter |
|
working power supply |
AC220V±10%,50Hz |
|
equipment output |
0~220Vrms,5Arms(20A peak value) |
|
output current |
0~150A |
|
Equivalent excitation voltage |
30KV |
|
Secondary winding |
range |
0.1~300Ω |
precision |
±0.5%,precision 0.1 |
|
Quadratic reality |
range |
5~1000VA |
precision |
±0.5% |
|
CT/PT Comparison measurement |
precision |
±4min |
CT/PT Angular difference measurement |
precision |
±0.05% |
CT Ratio measurement |
range |
1-10000 |
precision |
±0.5% |
|
PT Ratio measurement |
range |
1-10000 |
precision |
±0.1% |
|
work environment |
emperature: -10ºC ~ 40ºC, humidity: ≤90%, altitude: ≤2000m |
|
Size, weight |
Size: 380mm×240mm×180mm, weight: ≤12Kg |