• Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device
  • Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device
  • Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device
  • Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device
  • Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device
  • Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device

Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device

After-sales Service: Online
Warranty: 1 Year
Type: Current Injection Test System
Maxcapacity: <1000KN
Accuracy Grade: 1
Load Way: Electronic Load
Samples:
US$ 3000/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2023

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
KGJB-8033
Display
Digital
Control
Manual Control
Weight
20
Power Source
AC220V
Transport Package
Plywood Cases
Specification
42*19*50CM
Trademark
LONROY
Origin
Guangdong
HS Code
9024800000
Production Capacity
200

Product Description

KGJB-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device 

Product Introduction

KGJB-8033 microcomputer relay protection tester has 4 phase voltage and 3 phase current output, which can be easily used for various types of protection tests. It is an important test tool to ensure the safe and reliable operation of power system. It can independently complete the device testing in professional fields such as microcomputer protection, relay protection, excitation, measurement, fault recording, etc., and is widely used in scientific research, production and electrical test sites in electric power, petrochemical, metallurgy, railway, aviation and other industries.
KGJB-8033 microcomputer relay protection tester through a full set of Chinese operating software on the Windows platform, can carry out a variety of large complex and more automated verification work, can easily test and scan a variety of protection set values, can store test data in real time, display vector graphics, draw fault waveform, online printing reports, etc. The powerful software can complete a variety of large and complex calibration work with high degree of automation, such as three-phase differential test, plant power quick cutting, ready self-feeding test, line protection inspection and reclosing at the same time, etc., can easily test and scan a variety of protection set values, fault playback, real-time storage of test data, display vector graphics, online printing reports, etc.

 

KGJB-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device 

Product Characteristics
1, the standard 4-phase voltage and 3-phase current output has a 4-phase voltage and 3-phase current output, which can be easily carried out a variety of combined outputs for various types of protection tests. Each phase voltage can output 120V, current three and can output 90A, the fourth phase voltage Ux is a multifunctional voltage item, can be set to 4 kinds of 3U0 or detection voltage, or any voltage value of the case output.
2, the single machine operation is easy to operate by the convenient and flexible rotating mouse through the large screen LCD display, all Chinese display. It can complete most of the field test and verification work, can verify all kinds of relays and microcomputer protection, and can simulate all kinds of complex transient, permanent and transformational faults for whole group tests. Boot can be used, easy to operate.
3, double operation mode, connect the computer to run through the full set of Chinese operating software on the Windows platform, can carry out a variety of large complex and more automated verification work, can easily test and scan a variety of protection set values, can store test data in real time, display vector graphics, draw fault waveform, online printing reports, etc.
4, powerful software. It can complete a variety of large and complex calibration work with high degree of automation, such as three-phase differential test, plant power quick cutting, ready self-feeding test, line protection inspection and reclosing at the same time, etc., can easily test and scan various protection values, fault playback, real-time storage of test data, display vector graphics, online printing reports, etc.
5, switch quantity contact rich KDJB-702 for 7 contact input and 3 pairs of air contact output. Input contacts are null contacts and 0 ~ 250V potential contacts compatible, intelligent automatic recognition. Input and output contacts can be expanded according to user needs.
6, large screen LCD display. This machine adopts 320×24

 

KGJB-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device 

Product Parameters

 1,Ac current source
Three-phase current source with the same neutral point. The current rise and fall time is less than 100μs
Maximum output power: 400VA/ phase
Output accuracy:

0.1A~2A degree of accuracy  ±20mA
2A~10A degree of accuracy   ±0.2%
10A~40A degree of accuracy ±0.5%
 
definition:
0.1A ~ 10A resolution  1mA
10A ~ 40A resolution  5mA

Single-phase continuous output time:

0.1A to 10A The output time is unlimited
10A to 20A Output time ≥30 seconds
20A to 30A Output time ≥3 seconds
30A to 40A Output time ≥2 seconds

 

2,Ac voltage source
Voltage source with four phases sharing neutral point, current rise and fall time < 100μs
Maximum output power: ≥75VA/ phase
Output accuracy:

1V ~ 10V accuracy         ±20mV
10V ~ 125V accuracy   Plus or minus 0.2%

definition:

1V ~ 10V resolution          1mV
10V ~ 125V resolution     5mV

 

3,Dc current source
Single-phase output range: -10A to +10A or 0 to 20A
Maximum output power: 200VA/ phase
Output accuracy:

±0.1A ~ ±2A accuracy       ±20mA
±2A ~ ±10A accuracy        Plus or minus 0.5%

definition:5mA


4,Dc voltage source
Dc voltage output range: -150V ~ +150V or 0 ~ 300V
Maximum output power: ≥100VA
Output accuracy:

±1V ~ ±10V accuracy          ±20mV
±10V ~ ±150V accuracy     Plus or minus 0.5%

definition:

±1V ~ ±5V          resolution 5mV
±5V ~ ±150V     resolution 10mV

 

5,Ac voltage, current source Angle
Phase Angle range: 0° ~ 360°
Accuracy: ±0.2°
Resolution: 0.01°


6,Ac voltage, current source frequency
Frequency range: 10 ~ 1500Hz
It can superimpose 2 ~ 20 harmonics and DC of any amplitude
Output accuracy: ±0.2%
Resolution: 0.001Hz

 

7,Timing accuracy

1ms~1S

±10ms

1S~999999S                                         

±0.2%                                         

8, the amount of opening
8 independent switch contact inputs automatically identify the polarity of the active contact
Compatible with null contact and 15V ~ 250V active contact
9, out of quantity
4 pairs of programmable switch air contact output
Contact capacity: 250VDC, 0.5A or 250VAC, 0.5A
10. Synchronicity
Voltage and current synchronization ≤50μS
11. Power supply
Ac input voltage:
Rating: 220V±10%
Base value: 220V±2%
Ac power supply frequency:
Rating: 50Hz±10%
Reference value: 50Hz±2%
12. Use environment
Ambient temperature: -10ºC ~ +40ºC
Relative humidity: ≤90%
Atmospheric pressure: 80 ~ 110kPa
13, chassis size and weight
Box size (L x W x H) : 420mm x 190mm x 500mm
Weight: 20 kg

Kgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test DeviceKgjb-8033 Current Injection Test System Microcomputer 4 Phase Current Protection Test Device

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now