KGRB-III Transformer Winding Deformation Apparatus Machine Electric Sweep Frequency Response Analyzer
Product Introduction
KGRB-III transformer winding deformation tester has the function of linear sweep frequency measurement and segmented sweep frequency measurement dual measurement system, compatible with the current two domestic technical schools of measurement mode. The amplitude-frequency characteristic conforms to the technical index of the national amplitude-frequency characteristic tester. The horizontal coordinate (frequency) has two kinds of linear indexing and logarithmic indexing, so the printed curve can be a linear indexing curve or a logarithmic indexing curve, and users can choose according to actual needs.
KGRB-III transformer winding deformation tester adopts high-speed and highly integrated microprocessor for acquisition and control. High-speed dual-channel 16-bit A/D sampling (field test changes tap-changer, waveform curve changes).
KGRB-III transformer winding deformation tester mainly detects the amplitude-frequency response characteristics of each winding of the transformer, and compares the test results vertically or horizontally, and determines the winding deformation that may occur in the transformer according to the change degree of amplitude-frequency response characteristics.
KGRB-III Transformer Winding Deformation Apparatus Machine Electric Sweep Frequency Response Analyzer
Product Characteristics
1, acquisition control using high-speed, highly integrated microprocessor.
2. USB interface for communication between laptop and instrument.
3, the hardware movement adopts DDS special digital high-speed sweep frequency technology (USA), through the test can accurately diagnose winding distortion, bulge, shift, tilt, turn short circuit deformation and interphase contact short circuit and other faults.
4, high-speed dual-channel 16-bit A/D sampling (field test changes the tap-changer, the waveform curve has a clear change).
5, signal output amplitude software adjustment, the maximum peak ±10V.
6, the computer will automatically analyze the test results and generate electronic documents (Word).
7, the instrument has linear sweep frequency measurement and segmented sweep frequency measurement dual measurement system function, compatible with the current domestic two technical schools of measurement mode.
8, amplitude-frequency characteristics in line with the national amplitude-frequency characteristics tester technical indicators. The horizontal coordinate (frequency) has two kinds of linear indexing and logarithmic indexing, so the printed curve can be a linear indexing curve or a logarithmic indexing curve, and users can choose according to actual needs.
9, detection data automatic analysis system
The winding similarity is compared between the three phases A, B and C
The analysis results are as follows:
(1) The consistency is good
(2)Good consistency
(3)Poor consistency
(4)Poor consistency,
Longitudinal comparison A-A, B-B, C-C The winding deformation is compared between the original data and the current data in phase
The analysis results are as follows:
(1) Normal winding
(2) Mild deformation
(3)moderate deformation
(4)Severe deformation
10, can automatically generate Word electronic documents for saving and printing.
11, the instrument fully meets the technical conditions of the power standard DL/T911-2004 "Frequency response Analysis of power transformer winding deformation".
KGRB-III Transformer Winding Deformation Apparatus Machine Electric Sweep Frequency Response Analyzer
Product Parameters
3.1 Scan Mode
1. Linear scan distribution
Sweep frequency measurement range: (10Hz)-(10MHz)40000 sweep frequency, resolution of 0.25kHz, 0.5kHz and 1kHz.
2, subsection sweep frequency measurement distribution
Sweep frequency measurement range: (0.5kHz)-(1MHz), 2000 sweep frequency point;
(0.5 kHz) - (10 kHz)
(10kHz)-(100kHz)
(100kHz)-(500kHz)
(500kHz)-(1000kHz)
3.2 Other technical parameters
1, amplitude measurement range: (-120dB) to (+20dB)
2, amplitude measurement accuracy: 0.1dB
3, scanning frequency accuracy: 0.005%
4, signal input impedance: 1MΩ
5, signal output impedance: 50Ω
6, signal output amplitude: ±20V
7, in phase test repetition rate: 99.9%
8, measuring instrument size (length width height)340X240X210(mm)
9, instrument aluminum alloy box size (L W H)370X280X260(mm), wire box aluminum alloy box size (L W H)420X300X300(mm)
10. Total weight :20Kg
11, operating temperature: -10ºC to +40ºC Storage temperature: -20ºC to +70ºC
Relative humidity: <90%, non-condensing