KGDQ-15 High Voltage Bridge Fault Tester Cable Sheath High Resistance Fault Break Locator
Introduction
The high voltage bridge fault tester is designed based on the MURRAY bridge principle. It is suitable for the location of the breakdown point of various wires and cables after laying, the defect point without breakdown but the insulation resistance value is low, and the location of the outer sheath fault of high voltage cables. Of course, it can also be used to locate the defect points of various cables in the cable factory.
The equipment uses switching power supply to form a high voltage constant current source, uses high sensitivity amplifier and galvanometer to indicate balance, and forms a balance bridge with proportional potentiometer, and the whole is placed at high potential. The test wire is a specially designed double-core high-voltage rubber cable. The four-end resistance measurement method is adopted to avoid the error introduced by the lead resistance. The operating button on the panel is at the ground potential and the bridge is operated through the insulated rod. The high voltage constant current source and bridge are integrated in a portable industrial plastic case. Therefore, the equipment has high voltage, light weight, easy operation and safe use.
KGDQ-15 High Voltage Bridge Fault Tester Cable Sheath High Resistance Fault Break Locator
Main technical parameters
Test voltage: negative high voltage, 0 ~ 15kV, continuously adjustable
Maximum current: 30mA
Test scale accuracy: ± (0.2%·L±1) m
Burn-out voltage: 0 ~ 15kV, continuously adjustable
Burn-out current: 30mA
Working power supply: AC220V±10%
Anti-jamming capability: > 100VAC
Weight: ≤12kg
Dimensions: L450mm × W330mm × H320mm
KGDQ-15 High Voltage Bridge Fault Tester Cable Sheath High Resistance Fault Break Locator
Feature
1, DC voltage test: the equipment can output 0 ~ 15kV DC voltage, can be used for cable DC voltage test.
2, burn through the fault point: burn through and reduce the resistance of high resistance and flashover type fault point.
3, fault positioning: The use of bridge principle for positioning, four-end resistance measurement method to avoid the introduction of lead resistance error.