Customization: | Available |
---|---|
After-sales Service: | Online |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CT/PT transformer calibration machine/Measurement and control device accuracy tester
Product overview
KDHG-605A measurement and control device accuracy tester is A high-precision power source and high-precision multi-functional standard table integrated equipment developed by Wuhan Kaidi Zhengda Electric Co., Ltd. to meet customer requirements. The standard source part is based on 1.2G MAC DSP, large-scale FPGA, high-speed and high-precision D/A And a new generation of high-precision standard power source composed of high-fidelity power amplifier. It is suitable for electrical measurement, thermal engineering, remote motion, dispatching and other power departments and enterprises that need measurement, inspection and high-precision standard signal sources, and also suitable for other fields that need high-precision standard signal sources for measurement and inspection. At the same time, the equipment is equipped with 5 switching input and 4 switching output. Can cooperate with customers to complete some remote control, remote letter test work.
KDHG-605A can output power frequency (40Hz~65Hz) frequency, phase and amplitude adjustable high-precision voltage and current, is a very high-precision adjustable voltage and current standard source. The KDHG-605A can output very pure sinusoidal voltage and current with a distortion of less than 0.1% and a typical value of 0.03%. The voltage and current output of the KDHG-605A has a very high output stability, with a typical value of 0.004% RD. Therefore, it is very suitable for use in the workplace that requires high-precision inspection and calibration, such as the measurement department for the detection of various voltage, current, power and other electric parameter meters.
KDHG-605A can also measure three-phase voltage, current, frequency, phase, active power, reactive power, electric energy and other parameters, and can measure waveform distortion and 2~50 harmonics, the upper configuration software integrates more abundant and convenient operation items.
CT/PT transformer calibration machine/Measurement and control device accuracy tester
Product characteristics
1, can output pure, distortion degree in 0.03% (typical value) sinusoidal power signal.
2. Each harmonic output can be superimposed on the fundamental wave.
3, frequency output 40Hz~65Hz adjustable, resolution 0.002Hz, accuracy 0.002Hz.
4, the AB phase is a frequency benchmark, and the C phase is a separate frequency benchmark, so it can be divided into phases.
5, phase 0~360 degrees adjustable, can easily simulate a variety of power supply conditions, and even reverse power supply situation.
6, strong load capacity, can carry capacitive, inductive, resistive load or composite load, and the load adjustment rate is better than 0.01% RG.
7, good temperature stability, the core device is a military-grade product with a temperature coefficient as small as 1PPM, which can ensure the output accuracy in the outdoor temperature environment.
8, using 32-bit MCU+DSP processor, strong and flexible functions.
9, power frequency weekly wave up to 50000 points of the waveform kneading, internal signal output without filter smooth filtering, to ensure the accurate output of the waveform, so that the system can output accurate harmonics, but also make the system has excellent harmonic distortion index.
10, perfect overcurrent, overvoltage, overheating, short circuit, open circuit, overload protection.
11, hardware PID, fast response, load changes will not cause the slightest fluctuation in the output.
12, open communication protocol, convenient secondary development (RTU/FTU/ power management terminal/public metering terminal factory automatic inspection.
13, can be with pure capacitive load.
14, can output 0~±10V, 0~20mA signal for verification transmitter.
15, can measure voltage, current, power, electric energy, harmonics and other power.
16, can measure 0~±10V, 0~24mA small DC signal.
17, can output 0~250V high-precision DC signal.
18, equipped with 5 switch input,4 switch output to the user to do the corresponding test experiment.]
CT/PT transformer calibration machine/Measurement and control device accuracy tester
1.AC voltage output | |
Adjustment fineness | 0.01%RG |
Accuracy | better than ±0.05%RG |
Stability | better than ±0.01%RG/1min |
Distortion degree | better than 0.1% (non-capacitive load) |
Output power | rated 15VA per phase |
Full load adjustment rate | less than ±0.01%RG |
Full load adjustment time | less than 1mS |
Output range | 0~120V |
Gear setting | 0~57.7V, 57.7V ~120V |
Temperature drift | ±8PPM/ºC |
Long-term stability | 60PPM/ year |
2.AC current output | |
Adjustment fineness | 0.01%RG |
Accuracy | better than ±0.05%RG |
Stability | better than ±0.01% RG /1min |
Distortion degree | better than 0.1% (non-capacitive load) |
Output power | rated 15VA per phase |
Full load adjustment rate | less than 0.01%RG |
Full load adjustment time | less than 1mS |
Output range | current 0~6A |
Gear setting | 0~1A, 1~6A. |
Temperature drift | ±8PPM/ºC |
Long-term stability | 60PPM/ year |
3.DC signal output | |
DC voltage output | 0~250V |
Accuracy | better than ±0.05%RG |
Rated power | rated 15VA |
4.small DC signal output | |
Small DC voltage output | -10V~10V |
Small DC current output | 0~20mA |
Accuracy | better than ±0.05%RG |
Stability | 0.01%1min |
5.Power output | |
Accuracy | better than ±0.05%RG |
Stability | better than 0.01%1min |
6.Phase | |
Adjustment range | 0~359.99 degrees |
Resolution | 0.01 degrees |
Accuracy | ±0.03 degrees |
7.Frequency | |
Adjustment range | 40Hz~65Hz |
Resolution: | 0.002Hz |
Accuracy | ±0.002Hz |
Temperature drift: | ±0.5PPM/ºC |
Long-term stability | ±4PPM/ year |
8. Power factor | |
Adjustment range | -1~0~+1 |
Resolution | 0.0001 |
Accuracy | 0.0005 |
9. Open in and out | |
Switching input | 5 channels, compatible with empty node and active node input, active input is 0¬5V signal. |
Switching output | 4, the first 3 for MOS tube output, the fourth for relay output. |
10, input voltage measurement | |
Voltage measurement resolution | 0.01%× gear |
Voltage measurement accuracy | 0.05%RG,0~420V |
11, input current measurement | |
Current measurement resolution | 0.01%× gear |
Voltage measurement accuracy | 0.05%RG,0~10A |
12, input power measurement | |
Active power accuracy | 0.05%RG,0.05A-10A 30V-420V PF≥0.5 |
Reactive power accuracy | 0.1%RG,0.05A-10A 30V-420V PF≥0.5 |
13, electrical energy pulse output | |
Active energy accuracy | 0.05%RG,0.05A-10A 30V-420V PF≥0.5 |
Reactive energy accuracy | 0.1%RG,0.05A-10A 30V-420V PF≥0.5 |
14, electrical energy pulse input | |
Active energy accuracy | 0.05%RG,0.05A-10A 30V-420V PF≥0.5 |
Reactive energy accuracy | 0.1%RG,0.05A-10A 30V-420V PF≥0.5 |
15. Phase measurement | |
Phase measurement range | -180.00~+180.00° or 0°~359.99° |
Phase measurement accuracy | 0.05° (current ≥200mA, voltage ≥30V) |
Resolution | 0.001° |
16. Frequency measurement | |
Frequency measurement range | 40Hz~65Hz |
Frequency measurement resolution | 0.001Hz |
Frequency measurement accuracy | 0.005Hz |
17, power factor measurement | |
Power factor measurement range | -1.0~0~+1.0 |
Power factor measurement resolution | 0.0001 |
Power factor measurement accuracy | 0.0005 |
18, harmonic measurement | |
Harmonic measurement range | 2~50 times |
Harmonic measurement accuracy | 0.4%RG |
19, small signal DC measurement | |
DC voltage measurement range | -10V~10V |
DC current measurement range | 0~24mA |
working power supply | 220V (± 5%) AC@50Hz. |